http://www.grewayelectric.com We are testing a 22kW Generac Generator Water Column (gas pressure) for Liquid Propane. We should have 10-12 inches of Water Column and it should not drop below One Water Column during the following: Engine In Standby Mode Engine Cranking During Startup Running Without A Load Running With A Load Applied To The Generator And, Full Load Applied To The Generator In this video you will see we maintain the required water column throughout all the tests given. The gauge flickering