We are testing a 22kW Generac Generator Water Column (gas pressure) for Liquid Propane. We should have 10-12 inches of Water Column and it should not drop below One Water Column during the following:
Engine In Standby Mode
Engine Cranking During Startup
Running Without A Load
Running With A Load Applied To The Generator
And, Full Load Applied To The Generator
In this video you will see we maintain the required water column throughout all the tests given. The gauge flickering